The most likely fix on an UltraTemp alarm: check water flow before you touch anything inside the cabinet. The UltraTemp doesn't throw numeric codes — it lights a red SERVICE light and spells the problem out in words on the LCD. The two messages I see most on South Florida pads, LOW WATER FLOW and HIGH REFRIG, share the same first three causes in Pentair's own troubleshooting table: the pump is off, flow is too low, or an external bypass valve is open. Clean the filter, set the valves, reset once, and most of these calls end there. Every alarm below comes from Pentair's UltraTemp manual; a few thresholds shifted between revisions, so check yours.
This covers the heat-pump-only UltraTemp, 70 through 140, including the H/C heat-and-cool models. Pentair's 2010 guide lists the same alarm messages for the ThermalFlo HP. The UltraTemp ETi hybrid, a heat pump and gas burner in one cabinet, has its own manual and isn't covered here. For a gas Pentair heater, see our MasterTemp 400 error code guide.
How the UltraTemp tells you something is wrong
Three panel features save real time:
- The alarm history. The board stores the last 30 alarms. From the ALARM STATUS screen, press the DOWN arrow — the first entry is the most recent.
- The five-minute restart delay. When the unit is turned on or reset, the compressor waits five minutes to protect itself. A fan running with no cool air out the top during that window is normal.
- The input status screen. In the service menu (press UP and DOWN together), a tech can read a 1 (on) or 0 (off) for the water flow switch (WF) and the high and low refrigerant pressure switches (HP, LP).
UltraTemp alarm message quick reference
| Message | What Pentair says it means | Causes Pentair lists | DIY or pro? |
|---|---|---|---|
| LOW WATER FLOW | The pressure switch sensing water flow is open | Pump off, not enough flow, external bypass open, or a bad water pressure switch | Flow checks DIY; switch is pro |
| HIGH REFRIG | The refrigerant high-pressure switch is open | The same three flow causes first (minimum flow is 30 GPM), then a bad switch, a TXV stuck closed, or an overcharged system | Flow DIY first; refrigerant side pro |
| LOW REFRIG | The refrigerant low-pressure switch is open | Air and water too cold to run, restricted airflow through the coil, a faulty fan, a bad switch, a TXV stuck closed, or low refrigerant from a leak | Airflow DIY first; refrigerant pro |
| FIVE ALARMS | Five faults in one hour | Another alarm is repeating; resets itself in an hour or with ON/OFF | Read the history |
| BROWNOUT | The 24 VAC supply to the control board is low | Bad transformer or low supply voltage to the unit | Pro — electrical |
| HIGH WATER TEMP | Water above 107°F (older manuals list 108°F or 109°F) | Bad water thermistor or control board | Pro |
| LOW WATER TEMP | Water below 40°F (45°F in the 2010 manual) | Bad water thermistor or control board | Pro |
| WATER THERM SHORT / OPEN | Water temperature thermistor circuit shorted or open | Thermistor or control board — 10k-ohm resistance test | Pro |
| SUCTION TH SHORT / OPEN | Defrost thermistor circuit shorted or open | Thermistor or control board — same test | Pro |
| REMOTE POOL/SPA | Pool and spa remote inputs energized at the same time | Automation output wiring | Pro |
| SERIAL COMM LOST | No message from the automation controller for two minutes (2016 manual) | RS-485 link to IntelliTouch or EasyTouch | Pro |
Fix before you call: the order I work every UltraTemp alarm
- Read the message and the history. If it says FIVE ALARMS, scroll back — Pentair notes the alarm repeating underneath most likely caused the lockout.
- Confirm the pump is running at a real speed. The UltraTemp needs at least 30 GPM. A variable-speed pump on a low overnight speed can fall short.
- Clean the filter and empty the baskets. Pentair lists dirty filters, a clogged pump impeller, and suction air leaks under low flow.
- Set the valves. Close any external bypass around the heat pump and set every other valve to send water through it. A pool-spa valve left on spa is a classic low-flow trap.
- Clear the airflow. Pentair calls for 24 inches clear in front, 12 inches on the other sides, and 5 feet above under an overhang. Pull leaves off the coil, trim shrubs, and hose a dirty coil gently — never a pressure cleaner.
- Reset once. Press ON/OFF to clear the alarm, wait out the five-minute delay, and watch a full start.
- Stop if it comes back. The same alarm with verified flow and a clean coil means a switch, the TXV, the refrigerant charge, or the electrical supply. That's licensed work.
LOW WATER FLOW: the switch is usually telling the truth
The UltraTemp won't run until its water pressure switch closes, and Pentair presets that switch at 1.5 psi. The manual's four causes run in the order I'd check them anyway: pump off, not enough flow, an open bypass, and only then a bad switch, which a tech confirms with a resistance check while water is flowing. On Florida routes since the late 1990s, I've cleaned far more filters behind this alarm than I've replaced switches.
A very short return line to the pool may not build enough back pressure to close the switch; Pentair's fix is a directional fitting where the return enters the pool. And the switch is adjustable, but Pentair warns that setting it to close at too low a flow can damage the appliance. That adjustment is a tech job.
HIGH REFRIG: usually a flow problem wearing a refrigerant label
HIGH REFRIG means the refrigerant high-pressure switch opened. People assume a recharge, but Pentair's first three causes are the same flow problems behind LOW WATER FLOW: when water isn't carrying heat away fast enough, refrigerant pressure climbs until the switch trips. Pentair also lists a unit plumbed backwards — the manual puts the inlet on the right side and the outlet on the left — and a heat exchanger clogged with debris.
On a heat pump that hasn't run for an extended period, Pentair says to check the pool water level and cycle the unit on and off up to three times before calling for service. Past that, the remaining causes — a failed switch, a TXV stuck closed, or an overcharged system — are work for an EPA 608-certified tech.
LOW REFRIG: a cold morning or a leak
LOW REFRIG means the low-pressure switch opened. A leak is on Pentair's list, but so are air and water temperatures too cold to operate the heat pump — and the manual's fix for that one is to wait for warmer temperatures and see if it runs. On a January cold-snap morning in Palm Beach County, that's the first thing I consider. Next come restricted airflow through the coil, a faulty fan (capacitor, motor, or a slipping blade), a bad switch, and a TXV stuck closed.
A real leak means find it, repair it, pull a vacuum, and recharge — sealed-system work that federal law reserves for EPA Section 608-certified techs. Topping off without finding the leak just schedules the next call.
Defrost is not a fault
The UltraTemp may enter defrost when the air is around 50°F, if defrost is enabled in the service menu. The documented cycle is passive: the compressor stops, the fan runs about 15 minutes, and the compressor restarts only if the refrigerant sensor reads 20°F above the defrost start point — otherwise the unit shuts down. A heat pump that goes quiet on a cold morning may be doing exactly what it was designed to do. Pentair also lists an Active Defrost 140 H/C, so confirm which you have. If ice stays on the coil, shut the unit off, let it thaw, and fix the cause. More in our heat pump defrost guide.
The sensor and power messages
WATER THERM SHORT or OPEN, SUCTION TH SHORT or OPEN, HIGH WATER TEMP, and LOW WATER TEMP all point at a thermistor or the control board. Check the real water temperature with a thermometer first. South Florida pool water doesn't get anywhere near 40°F, so LOW WATER TEMP here is a sensor problem until proven otherwise. A tech measures the thermistor against Pentair's 10k-ohm chart — about 10,000 ohms at 77°F — and replaces it if it reads shorted or open, or replaces the board if it tests good.
BROWNOUT means the 24-volt supply to the board is low. Pentair's numbers are 208–260 volts into the transformer and 24–28 volts out. Low output means a new transformer; low supply means a lost phase or a voltage sag that may need a boost transformer near the unit. Pentair warns that voltage below 208 can damage the heat pump, and a breaker that keeps tripping goes to a certified electrician.
REMOTE POOL/SPA and SERIAL COMM LOST are automation issues: the first is fixed in the automation output, and for the second, the heat pump's RS-485 address must match the controller.
No alarm, but no heat
A fan running with no cool air out the top is the five-minute delay or a compressor, capacitor, or contactor problem. A fan that won't turn points to the fan relay, capacitor, motor, or board. A pool that heats slowly with no alarm usually isn't broken: Pentair lists low flow, cold air, too short a pump run, no cover, wind, and shade, and says a heat pump is built to hold a temperature, not heat fast.
South Florida failure modes
- Salt air on coastal pads. Pentair's manual flags salt water near the coast. Oceanside coils and connectors corrode years ahead of inland units, and a corroded sensor connector can look like a dead sensor — we check connections before ordering parts. Rinse the coil with fresh water.
- Cold snaps. Output drops as the air cools, so a few January mornings a year bring LOW REFRIG or a defrost shutdown on a healthy unit. Run it during the warmest part of the day.
- Condensate. The UltraTemp normally drains 3–5 gallons an hour while running, more when it's humid. A puddle under a running unit is usually condensate — test it for chlorine. Water that keeps draining more than an hour after shutdown points to an internal leak.
What it costs, and when to replace
A diagnostic runs $0–$125, and it's free for our weekly-route clients. Most heater repairs — the sensors, pressure switches, relays, and control boards behind most UltraTemp alarms — land between $250 and $1,800. A failed compressor or heat exchanger runs $4,000–$5,000, and a new heater installed is $5,000–$7,000. When a compressor quote gets that close to a new unit on an older heat pump, I'll tell you to put the money toward the replacement.
When to call a pro
The filter, baskets, valves, clearances, and a gentle coil rinse are yours. Everything past that is licensed work. At Florida's Best Pool Service, repairs are managed by us under our Florida Certified Pool/Spa Contractor license. We do most of the work ourselves and bring in licensed specialists when a job needs one: an EPA 608-certified tech on the refrigerant side, or an electrician for a new circuit. For the same first checks on any brand, see our pool heater problems guide; AquaCal owners can use the AquaCal heat pump troubleshooting guide. When you're ready, book a pool heater repair visit and we'll diagnose it with a written quote before any part is ordered.
Pool heater sizing calculator
Surface area × temperature rise × 12 = required heater output. Surface area drives it — evaporation is where pools lose heat.
84–88°F is the family sweet spot.
South Florida unheated pools sit in the low-to-mid 70s most winters and can dip into the 60s after a hard cold front; size for the cold weeks.
Gas heater: 200k BTU nameplate
A 19°F rise on 392 sq ft needs ≈ 89,000 BTU/hr of output (≈ 109k input at ~82% efficiency). Oversizing a gas heater is fine — it just reaches temperature faster. Undersizing means it runs forever on cold weekends. Heat pumps are rated differently (typically 110k–140k BTU output) and heat slower but far cheaper per degree — the right call for set-and-hold temperature in South Florida; gas wins for fast weekend heat-ups.
Reference sizing for an uncovered residential pool with typical wind exposure, per manufacturer surface-area charts. A solar cover cuts the real load dramatically. Final sizing and gas-line capacity are the installer's responsibility.
Book heater service·Get a heater sized and installed·My heater needs repair
Frequently asked questions
It means the water pressure switch that proves circulation is open, so the heat pump will not run. Pentair's troubleshooting table lists four causes in this order: the circulation pump is not on, there is not enough water flow, an external bypass around the heat pump is open, or the pressure switch itself is bad. Clean the filter, empty the pump and skimmer baskets, close any bypass, and make sure every other valve sends water through the heat pump. If the alarm stays with good flow, a tech checks the switch's resistance with water flowing and replaces it if it reads open.
Usually not. HIGH REFRIG means the refrigerant high-pressure switch opened, and Pentair lists the same first three causes as LOW WATER FLOW: the pump is off, flow is too low, or an external bypass is open. The manual's minimum flow is 30 GPM. Pentair also lists a unit plumbed backwards and a heat exchanger clogged with debris, and notes the alarm can appear on a unit that has not run for an extended period, in which case it says to check the pool water level and cycle the heat pump on and off up to three times before calling for service. Once flow checks out, the remaining causes are a bad switch, a TXV stuck closed, or an overcharged system, and that is work for an EPA 608-certified technician.
The refrigerant low-pressure switch opened. A leak is one cause, but Pentair also lists air and water temperatures too cold for the heat pump to operate, restricted airflow through the coil, a faulty fan (check the capacitor, the fan motor, and whether the blade is slipping or broken), a bad low-pressure switch, and a TXV stuck closed. For the cold-weather cause, the manual's advice is to wait until temperatures warm up and see if the unit runs. If it is a leak, the fix is to find and repair it, pull a vacuum, and recharge, which legally requires an EPA Section 608-certified tech.
FIVE ALARMS means five faults of any kind happened within one hour. It resets automatically after an hour, or you can clear it by pressing the ON/OFF button. Clearing it does not fix anything. Pentair's note is that the alarm that keeps repeating most likely caused the lockout, so scroll the alarm history with the DOWN arrow from the ALARM STATUS screen and deal with the message that shows up over and over.
Press the ON/OFF button to clear the alarm, then give it time. The compressor has a five-minute restart delay to protect itself, so a fan running with no cool air out the top during those five minutes is normal. Reset once, after you have checked flow, valves, and airflow. If the same alarm returns, stop resetting and get it diagnosed, because repeated resets do not fix a failed switch, sensor, or refrigerant problem.
It may be defrost doing its job. Pentair's manual says the UltraTemp may enter defrost when the air is around 50 degrees, if defrost is enabled in the service menu. The documented cycle stops the compressor and runs the fan for about 15 minutes; the compressor restarts only if the refrigerant sensor reads 20 degrees above the defrost start point, and otherwise the unit shuts down. Pentair also lists air and water too cold to operate as a cause of LOW REFRIG. Heat pump output drops as the air cools, so run it during the warmest part of the day.
Probably not. Pentair says the UltraTemp normally produces three to five gallons of condensate an hour while running, and more in humid weather, which in South Florida is most of the year. Test the water for chlorine, because condensate has none. If drainage is above that range while it runs, or water keeps draining from the base more than an hour after the unit stops, Pentair says an internal plumbing leak may have occurred and a qualified heat pump tech should look at it.
The 24-volt supply to the control board is low. Pentair's numbers are 208 to 260 volts into the transformer and 24 to 28 volts out. If the transformer output is low, the transformer gets replaced. If the supply itself is low, the causes are a lost phase or a voltage sag, and Pentair says a boost transformer closer to the heat pump may be needed. The manual also warns that voltage below 208 can damage the unit. This is electrical work for a licensed tech, and a new circuit is a job for an electrician.
A diagnostic runs $0 to $125 and is free for our weekly-route clients. Most heater repairs, including the sensors, pressure switches, relays, and control boards behind most UltraTemp alarms, land between $250 and $1,800. A failed compressor or heat exchanger runs $4,000 to $5,000, and a new heater installed runs $5,000 to $7,000, so on an older unit a compressor quote is usually the point to put the money toward a replacement. Before any of that, clean the filter and check the valves, because the flow alarms are the ones we see most.
Pentair's 2010 installation guide covered the ThermalFlo HP and the UltraTemp together and lists the same alarm messages, so ThermalFlo owners can use this list, though the temperature thresholds differ by manual revision. The UltraTemp ETi is a hybrid that pairs a heat pump with a gas burner and has its own installation and user's guide, so use that manual for its alarms. This guide covers the heat-pump-only UltraTemp.
UltraTemp still showing an alarm after the flow check?
Most LOW WATER FLOW and HIGH REFRIG calls end at the filter and the valves. If flow is good and the alarm keeps coming back, we diagnose Pentair UltraTemp heat pumps across Palm Beach and Broward, with refrigerant work handled by an EPA 608-certified tech. Quoted in writing before any part is ordered.