Nine times out of ten, a little water on the pad is just condensation.But if it's a lot of water clearly coming from the unit, that often points to a failed heat exchanger, which typically means a new heater. Noises sort out the same way: most heater sounds are normal, and a few mean a part is failing. I've been on Florida routes since the late 1990s — my father has been a licensed Florida pool contractor since 1989 — and most of these calls get settled from the pad with a test strip. This page covers leaks and noises only. For a heater that isn't heating, start with our pool heater troubleshooting guide or our heat pump not heating guide.
Leaks: is that water actually a problem?
Heat pumps sweat, and in Florida they sweat a lot
A heat pump's cold coil wrings moisture out of the air like a glass of iced tea in July, and the water drains out through the base pan. Pentair and Hayward both put normal condensation at about three to five gallons an hour while the unit runs, more in humid air. In a South Florida summer that is a real puddle, all day long. It isn't a leak; just keep the drain holes in the base clear. The base pan also catches rain, roof runoff, and sprinkler spray, and on a cold morning frost melts off the coil during defrost. All of that is normal.
The two tests that settle it
Condensation and rain have no chlorine in them. Pool water does.
- The test strip.Catch water dripping from the heater itself, not the puddle around it, and dip a chlorine test strip in it. No chlorine means condensation or rain. On a bromine pool, use a bromine strip — AquaCal's manual says to test for whichever sanitizer you use.
- The shutdown test. Turn the heat pump off and leave the pool pump running. Condensation stops when the unit stops. Pentair says water still draining from the base more than an hour after shutdown may mean a leak in the internal plumbing; Hayward and AquaCal say to give it several hours.
One trap: water travels across a pad. A weeping pump seal or backwash water can run under a dry heater and test positive. Follow the wet trail uphill before you blame the heater.
Gas heaters drip too, briefly
Burning gas makes water vapor, and on a cold start it condenses on the cool heat exchanger and drips, sometimes onto the burners with a sizzle. A Pentair commercial manager writing in Pool & Spa Marketingcalled brief start-up condensation normal for most pool heaters, and Hayward says one of its gas models can make a few ounces to a couple of gallons of condensation an hour. It should taper off as the water warms — down here, mostly on the first cold-front start of the winter. One that never dries out is worth a look.
When it is a real leak
- At the unions where the plumbing connects: usually an O-ring or a union that needs reseating, the smallest leak there is.
- At the header, the water manifold on the side of a gas heater: a worn header gasket, which is a gasket repair and one of the replacement items on our heater maintenance checklist.
- From inside the cabinet: water in the burner tray, rust or crust on the exchanger tubes, or chlorinated water from a heat pump that has been off for hours. That's the heat exchanger or the internal plumbing, and usually a replacement conversation.
Hayward lists four reasons a heat exchanger leaks: chemical imbalance, sanitizer damage, freeze damage, and failed joints. Freezes are rare here; the other three are not. Low pH corrodes an exchanger, and chlorine tablets in the skimmer send concentrated sanitizer straight through it — Hayward's HeatPro manual says never do that, and to put any chlorinator downstream of the heater behind a check valve. Hayward also warns that flow above a heater's maximum can thin the tube walls.
If you can physically see the unit leaking, turn the heater off, shut the pool pump off, and call. Running it can make the damage worse.
Noises: what's normal and what isn't
Heat pumps
Normal is a steady fan whoosh, a compressor hum, and a click when the contactor pulls in. The compressor waits a few minutes after a call for heat — three on Hayward's HeatPro, five on Pentair's UltraTemp — and on a cold morning it may stop while the fan clears frost. Neither is a failure.
- Rattling or buzzing:a loose panel or screw, debris in the fan, a pipe vibrating against the cabinet, or a unit not sitting level — the usual suspects on heat pump maker Poolstar's own list. Breaker off, clear the debris, and check for anything loose.
- Grinding, squealing, or scraping: usually the fan motor bearings, or the blade touching the guard or ice. Bearings get worse in stages, the way a pump motor's bearings do. Shut it off and call.
- A loud clank, knock, or screech from the compressor: compressor territory. Shut it off and have it diagnosed.
- A steady hiss with the heat falling off: possibly refrigerant escaping, which is EPA Section 608 work. Our AquaCal guide covers the oily-joint signs of a refrigerant leak.
And confirm it's the heater. The pool pump a few feet away is often the real source of the racket.
Gas heaters and kettling
Normal is the blower spinning up on fan-assisted models, the igniter clicking, a soft whoosh as the burners light, and a steady roar. Kettlingis a popping, rumbling, or banging, like a kettle about to boil, while the heater runs — water flashing to steam against the hot exchanger tubes. Hayward's troubleshooting guide warns that flow below the minimum can boil the water, trip the high limits, and damage the heat exchanger. Two causes:
- Low flow: a dirty filter, packed baskets, a half-closed valve, or a variable-speed pump turned down too low. Rule this out first.
- Scale:South Florida fill water is hard, and high pH, alkalinity, or calcium scales the tubes — another cause on Hayward's failure list. Scale narrows and insulates the tubes, so spots overheat even with decent flow.
Fix flow first. If the banging continues with good flow, shut the heater off and have the exchanger checked for scale. A kettling heater is cooking its own exchanger.
- A boom or loud rumble at ignitionis delayed ignition from dirty burners or a weak spark. Shut it down and get it serviced — that's a safety problem, not a noise problem.
- A sizzlethat fades as a cold start warms up is condensation on the burners. One that won't quit, especially with water under the heater, can be pool water leaking onto the burners. Turn it off and call.
- A whistle or whine is usually water squeezing through a partly open valve or a sticking internal bypass, and less often the gas supply or the blower. Open your valves fully; past that, call a tech.
If you smell gas, none of this applies.Don't flip switches or relight anything. Shut the gas off at the meter or tank if you can do it safely, leave the pad, and call the gas utility. More in our pool heater safety guide.
What you see or hear, what it means, what to do
| What you see or hear | What it usually means | What to do |
|---|---|---|
| Steady drip from a running heat pump, worse when humid | Condensation | Strip-test once; keep the drain holes clear |
| Water under a heat pump after rain, sprinklers, or a cold morning | Rain, runoff, or defrost meltwater | Nothing |
| Gas heater drips after a cold start, then dries up | Exhaust condensing on a cold exchanger | Normal in short bursts |
| Drip at a union or at the header | O-ring or header gasket | Repair |
| Water with chlorine in it, or draining more than an hour after shutdown | Internal plumbing or heat exchanger leak | Heater off, pool pump off, call |
| Water in the burner tray, rust or crust on the tubes | Heat exchanger failure | Off and call — usually a replacement |
| Heat pump rattle or buzz | Loose panel, debris, a pipe touching the cabinet, an unlevel pad | Breaker off, clear and check. Still rattling — call |
| Grinding, squealing, or scraping | Fan motor bearings or the blade touching something | Shut it off and call |
| Compressor clank, knock, or screech, or a steady hiss | Compressor trouble or a possible refrigerant leak | Shut it off; licensed tech |
| Gas heater popping or kettling while it runs | Water boiling from low flow or scale | Fix flow. Still kettling — have the exchanger checked |
| Boom or loud rumble at ignition | Delayed ignition | Shut down and service now |
| Sizzle that won't quit | Possible water leaking onto the burners | Turn it off and call |
| Whistle or whine | Partly open valve or sticking internal bypass | Open the valves. Still whistling — tech |
| Smell of gas | Possible gas leak | Gas off if safe, leave the pad, call the gas utility |
The homeowner-safe check sequence
Nothing here opens the cabinet.
- Note when it happens— only while the heater runs, after rain, on a cold start, or at a low pump speed. The timing alone solves a lot of these.
- Trace the water uphill and rule out the pump, filter, and backwash line.
- Strip-test water dripping from the heater itself. No chlorine, or no bromine on a bromine pool, means condensation or rain.
- Run the shutdown test. Heater off, pool pump on. Check after an hour and again after a few hours.
- Check the unions for a drip right at the plumbing connections.
- For popping or banging, fix flow.Clean the filter and baskets, open every valve, and raise a variable-speed pump's speed.
- For rattles, turn the breaker off, clear the top grille and the coil, and look for anything loose or leaning on the cabinet.
Where the homeowner stops
Stop and call when the strip says pool water, when water comes from inside the cabinet, when banging survives a flow fix, or for any grinding, screeching, steady hissing, or gas smell. At Florida's Best Pool Service, heater repairs are managed by us under our Florida Certified Pool/Spa Contractor license. Our own techs handle most of the work; gas-side work goes to a licensed gas contractor, and refrigerant work to an EPA 608-certified tech.
What the repair looks like
A diagnostic runs $0–$125 and is free for weekly-route clients. Most heater repairs land between $250 and $1,800. A failed heat exchanger or compressor runs $4,000–$5,000, and a new heater is $5,000–$7,000 installed, which is why a leaking exchanger on an older heater usually ends in a replacement rather than a repair. An annual heater cleaning or tune-up runs $150–$350, and that's usually when a small weep gets caught. Everything is quoted in writing before a part is ordered. If the strip says pool water or the banging won't stop, book a pool heater repair visit.
Water with no chlorine in it is condensation or rain. Water with chlorine in it is your pool leaving through the heater. One test strip answers most leak calls before anybody opens a cabinet.
Frequently asked questions
Most of the water under a heat pump is condensation, not a leak, and that is normal. The cold coil pulls moisture out of the air, and Pentair and Hayward both put normal condensation at about three to five gallons an hour while the unit runs, more in humid weather. In a South Florida summer that can leave a steady puddle all day. The base pan also catches rain and sprinkler water. To be sure, dip a chlorine test strip in water dripping from the heater itself: no chlorine means condensation. Chlorine means pool water is escaping, and that is a service call.
Burning gas makes water vapor, and when the heater fires on cold water that vapor condenses on the cool heat exchanger and drips out, sometimes onto the burners with a sizzle. Brief condensation on start-up is normal for most pool heaters, and it should taper off as the water warms. In South Florida it mostly happens on the first cold-front start of the winter. Water that keeps coming after the heater has warmed up, water that drips with the heater off, or a strip test that shows chlorine points to a real leak at the header gasket or the heat exchanger.
Kettling is a popping, rumbling, or banging sound, like a kettle about to boil, that a gas heater makes while it runs. Water against the hot exchanger tubes is flashing to steam, and the bubbles collapse against cooler water. Hayward warns that flow below a heater's minimum can boil the water, trip the high limits, and damage the heat exchanger. Low flow is the usual cause, from a dirty filter, packed baskets, a half-closed valve, or a variable-speed pump turned down too low. Scale inside the tubes from hard, high-pH water is the other. Fix flow first. If it keeps kettling with good flow, shut it off and have the exchanger checked for scale.
A steady fan whoosh, a compressor hum, and a click at start-up are normal. A rattle or buzz usually means a loose panel or screw, leaves or debris in the fan, a pipe vibrating against the cabinet, or a unit that is not sitting level. Grinding, squealing, or scraping usually means the fan motor bearings are failing or the blade is touching the guard or ice. A loud clank, knock, or screech from the compressor, or a steady hiss with the heat falling off, means shut it off and call a tech. Also confirm it is the heater, because the pool pump next to it is often the real source.
Not if the leak is pool water or the banging continues after you fix flow. If you can physically see water leaking from the unit, turn the heater off, shut the pool pump off, and call, because running it can make the damage worse. A kettling gas heater is boiling water inside its own heat exchanger, and Hayward warns that kind of low-flow boiling can damage the exchanger. Condensation and rain are the exceptions; they are normal and need nothing. If you smell gas, shut the gas off if you can do it safely, leave the pad, and call the gas utility.
It depends on where the water starts. A drip at a union or a header gasket is a repair, while chlorinated water from inside the cabinet usually means the heat exchanger. A diagnostic runs $0 to $125 and is free for our weekly-route clients. Most heater repairs land between $250 and $1,800. A failed heat exchanger or compressor runs $4,000 to $5,000, and a new heater is $5,000 to $7,000 installed, so a leaking heat exchanger on an older heater usually means replacement. Everything is quoted in writing before any part is ordered.
Strip says pool water, or the banging won't stop?
Condensation and rain need nothing. Chlorinated water from inside the cabinet, or kettling that keeps going after the filter is clean, means a part is failing. We diagnose leaking and noisy heaters of every major brand across Palm Beach and Broward — free for weekly-route clients, quoted in writing before any part is ordered, with gas work by a licensed gas contractor and refrigerant work by an EPA 608-certified tech.