| Manufacturer model | ETi 400 High Efficiency Heater, natural gas, ASME listed, P/N 461113 |
|---|
| BTU input | 400,000 BTU/hr |
|---|
| Thermal efficiency | 96% (tested per ANSI Z21.56:19/CSA 4.7:19 2019, section 5.10) |
|---|
| Heat exchanger | Titan-Tough direct-fire titanium, ASME certified construction; design temperature rise 30°F ±5°F |
|---|
| Fuel | Factory configured for natural gas; propane conversion kit P/N 476072 available |
|---|
| Emissions and certification | Certified for low NOx emissions by a third-party test lab and communicated to SCAQMD for Rule 1146.2; ASME certified, CSD-1 compliant, CSA certified to ANSI Z21.56/CSA 4.7 |
|---|
| Water flow | 40 GPM minimum, 120 GPM maximum (external bypass required above 120 GPM); maximum ΔT 35°F, minimum ΔT 25°F |
|---|
| Gas supply pressure | Natural gas 4" w.c. minimum to 10.5" w.c. maximum; propane 4" to 12" w.c.; maximum pressure change 2" w.c. |
|---|
| Gas pipe sizing (natural gas) | 3/4" not permitted; 1" to 20 ft, 1-1/4" to 90 ft, 1-1/2" to 200 ft |
|---|
| Venting | Category IV; Schedule 40 PVC, Schedule 80 CPVC or stainless steel. 4" pipe to 120 ft or 6" pipe to 300 ft, less 12 ft per 90° elbow and 6 ft per 45°. Vent gas under 170°F. With 4" pipe the Combustion Air Intake Kit (P/N 475971) must be installed; intake and exhaust at least 36" apart. |
|---|
| Condensate | 2 to 4 gallons per hour. Condensate Neutralizer Kit (P/N 475612) strongly recommended; horizontal vent runs slope back toward the heater at 1/4 inch per foot so condensate drains through the neutralizer. |
|---|
| Electrical | 120 or 240 VAC, 60 Hz, single phase; 15 A circuit; about 5 A at 120 VAC or 2.5 A at 240 VAC |
|---|
| Clearances | 6" from combustible surfaces on the top, exhaust side, header side and door panels; 3 ft between a roof or deck overhang and the top of the exhaust vent; 36" from an air conditioner, heat pump or another gas heater |
|---|
| Dimensions and weight | 40" L x 30" W x 46" H; 365 lb crate weight |
|---|
| Safety and diagnostics | Two stack flue sensors (SFS activates at 170°F, thermal fuses at 187°F), two automatic gas shut-off switches (150°F), high limit (135°F), air flow switches, water pressure switch and condensate float switch; last five error codes readable from the control pad |
|---|
| Controls and automation | 2-wire dry contact through the fireman's switch terminals for IntelliCenter, IntelliTouch or EasyTouch Control Systems, or a time clock. Pentair's ETi 400 manual documents no RS-485 connection. 180° rotating control panel for left or right plumbing orientation. |
|---|